In the case of a specimen having a finished seam oriented in the vertical position, the clamp is fitted to the seam so that the set screws push the seam material into a position such that the protrusion at the bottom of the clamp "throat" engages the base portion of the rolled side of the seam. For seams not having a "rolled" seam, the orientation of the clamp is not critical. In the case of a specimen having a finished seam in the horizontal position, the S-5! clamp(s) are attached to the seam so that the set screws are above the seam and accessible for tightening.
Up to three S-5! clamps may be tested on the same panel specimen. Place clamps on the panel seam, evenly spaced from each other, and so that the end of the lower clamp on the specimen (most leeward from load) is a minimum of 6" from the lower end of the specimen. The set screws of the clamps are tensioned to the stated tension using a torque wrench. Unless other specific instruction is given, tighten and verify all clamp set screws to indicated tension. Sequentially retighten set screws if necessary as panel seam material compresses. Mark the location of the clamp(s) on the panel seam so that any differential movement between seam and clamp can be monitored.
Procedure
Securely fasten the load cell arms to the hole(s) through the S-5! clamp using 7/16", or 3/8" diameter bolts as appropriate for the hole size. Beginning at the lowest clamp (closest to test bed), load each clamp with upward pull at .25 inch per minute (parallel to seam) until failure*. Photograph the specimen after testing.
Reporting
Record the tensile value in pounds at the failure* point along with the failure* mode for each S-5! clamp tested. Calculate and record "mean" values. Note any unusual observations of the specimen during testing, as well as a verbal description of the specific failure* observed if it is other than type "A" or "B." Record the date of test, date of report, name of lab, name of technician and execute the completed data sheet.
*Failure
For the purpose of this test, any of the following occurrences shall be considered "failure":
A. Disengagement of clamp from panel seam
B. Clamp displacement of a distance of more than 8 millimeters (.315")
C. Breakage or fracturing of clamp or fasteners
D. Strippage of the clamp set screws
E. Fracturing of any area of panel seam
F. Buckling or any other structural or severe cosmetic damage to panel seam